tag or keyword Search the whole station

HR -25℃~200℃
HR -25℃~200℃
HR -25℃~200℃

HR-25℃~200℃ cooling heating circulator

Only control of reactor temperature
  • Heating Power2.5kW~15kW
  • Cooling capacity1kW~15kW
  • Power range4kW~21kW
  • Medium accuracy±0.5℃
  • RefrigerantR404A/R507C
  • Weight150KG~320KG
  • Details

Parameters Detailed

● Working temperatures from -45°C to +250°C, cooling and heating
● With 2pcs of LED display controller, can show the setting temperature & actual value, and alarm value for overtemperature.
● Efficient fast, simple topping up liquid.
● Maximum process stability and reproducibility
● Ensure fast cooling at high temperature and can acheive 200℃ ~ -20℃ temperature control continuously.
● The cycle system is closed, there is no oil mist and water vapor happend, so as to assure the lab safety and heat transfer fluid lifetime.
● Use copeland brand compressor, circulation pump, stable performance and reliable quality.
● Self-diagnosis function; freezer overload protection; high-pressure switch, overload relay, thermal protection device, liquid low level protection, high temperature protection and temperature fault protection.

ModelHR-25NHR-35NHR-50NHR-70NHR-100NHR-150N
Temperature Range-25℃~200℃
ControllerPID adaptive controller
Temperature Controlheat-conducting medium outlet temp.control
Temperature FeedbackHeat-conducting medium temperature feedback PT100(measure inlet temperature and outlet temperature)
Temp. Accuracy±0.5℃
Heating Power2.5kW3.5kW5.5kW7kW10kW15kW
Cooling Capacity200℃2.5kW3.5kW5.5kW7kW10kW15kW
100℃2.5kW3.5kW5.5kW7kW10kW15kW
20℃2.5kW3.5kW5.5kW7kW10kW15kW
-5℃2kW3kW4.5kW6.6kW8kW12kW
-20℃1kW1.8kW2.8kW3.8kW4.6kW7kW
Circulation Pump FlowMax20L/minMax35L/minMax35L/minMax50L/minMax60L/minMax110L/min
Circulation Pump Pressure1.2BAR1.2BAR1.2BAR1.2BAR1.5BAR1.5BAR
Tank Volume8L13L15L18L22L30
Be equipped with extra connection of expansion tank(ZG1/2)
CompressorMitsubishiCopelandCopelandCopelandCopelandCopeland
EvaporatorPlate heat exchanger
Operation PanelDisplay setting temperature and outlet and inlet temperature, 7-inch color touch screen
Data RecordU disk data export, Excel form, error record
Temperature RecordRecord setting temperature, outlet and inlet temperature
Safety ProtectionSelf-diagnosis function; freezer overload protection; high pressure switch; overload relay; thermal protection device and other safety protection.
Closed Circulation SystemThe whole system is full closed circulation, there is no oil mist at high temperature and no water vapor at low temperature, pressure do not rise up when system is running. The system will supplement oil automatically at low temperature.
RefrigerantR-404A/R507C
Connection SizeZG1/2ZG3/4ZG3/4ZG3/4ZG1ZG1
Dimension(cm)air-cooled40*70*13045*70*16045*70*16055*70*17565*85*18570*85*185
Weightair-cooled150kg165kg235kg265kg290kg320kg
PowerAC 220V 50HZAC 380V 50HZAC 380V 50HZAC 380V 50HZAC 380V 50HZAC 380V 50HZ
4kW5.6kW (max)8kW (max)11kW (max)15.5kW (max)22kW (max)
Case MaterialCold rolled steel
OptionalMODBUS RTU Protocl,  RS 232 interface
Optional Power220V 60HZ three-phase,440V~480V 60HZ three phase

Configuration Details

The whole liquid circulation is a closed system. There is no absorption of water vapor at low temperature and no oil mist at high temperature. The heat transfer oil can work at a wide temperature. There is no solenoid valve in the whole circulation system.

Working Principle

Application: Various Reactors (Microchannels, Glass, Jacketed Reactors, etc.), Distillation or Extraction System, Laboratory, University, Research Institute, Aerospace, Automotive Industry, Semiconductor and Electrical Test, Chemical, Pharmaceutical, Petrochemical, Biochemical, Medical, Hospital, R&D Workshop, Aerospace, Biological and Other Industries.