tag or keyword Search the whole station

SUNDI -90℃~250℃
SUNDI -90℃~250℃
SUNDI -90℃~250℃

SUNDI -90℃~250℃(the system add pressure 3bar)

Temperature control of reactor and material
  • Heating Power3kW~80kW
  • Cooling capacity0.2kW~80kW
  • Power range8kW~170kW
  • Medium accuracy±0.5℃~±1℃
  • Material accuracy±1℃
  • RefrigerantR404A/R508B
  • Weight260KG~3150KG
  • Details

Parameters Detailed

● Working temperatures from -120°C to +350°C
● Previously unachievable performance
●Intelligent temperature control
● Maximum process stability and reproducibility
● Adop plate heat exchager, Pipeline heating, the fastest heating and cooling rates.
● High cooling power from 0.5 to 1200kW
● Large temperature range without fluid change
● Closed system, extend thermal fluid lifetime
● 7-inch, 10-inch color TFT touch screen display
● Comprehensive warning and safety functions
● Rapid cooling down from high temperature (from 300 °C)
● Use magnetic drive pump, solve the circulation pump leakage

Configuration Details

ModelSUNDI-925WSUNDI-935WSUNDI-955WSUNDI-975WSUNDI-9A10WSUNDI-9A15WSUNDI-9A25WSUNDI-9A38WSUNDI-9A60WSUNDI-9A80W
Temp. range-90℃~+250℃(the system add pressure 3bar)
Control ModeFeedback PID + Our special dynamic control calculation, PLC controller
Temp. controlProcess temp. control and jacket temp. control model
Temp. differenceSet or control the temperature difference between jacket oil and raw material process
Program Editor10 programs, each program can edit 40 steps.
Communication PortocolMODBUS RTU Protocol,RS485 interface
Material temp. feedbackPT100 OR 4~20mA or communication(normal: PT100)
Temp. feedbackThe temp. of three points: the inlet and outlet of equipment,  reactor material temp.(external temp. sensor)
Medium temp. acccuracy±0.5℃±1℃
Material temp. accuracy±1℃
Heating power kW2.53.55.57.5101525386080
Cooling capacity kW at250℃2.53.55.57.5101525386080
0℃2.53.55.57.5101525386080
-40℃22.85681220314864
-60℃1.11.92.83.24.2610162432
-80℃0.350.50.81.21.62.13.561115
-85℃0.20.30.50.70.851.31.93.568
Circulation pump max
L/min bar
2035355060110150200400400
22222.52.52.52.52.52.5
PumpLNEYA magnetic drive pumpGerman magnetic drive pump
CompressorTecumseh closed compressorDorin semi-closed compressor
Expansion valveEmerson thermal expansion valve/Emerson electronic expansion valve/danfoss thermal expansion valve.
EvaporatorDANFOSS/KAORI Plate heat exchanger
Operation Panel7-inch touch screen,show temp curve\EXCEL data output
Safety protectionSelf-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device, liquid low level protection, high temperature protection and temperature fault protection.
Closed circulation systemThe whole system is full closed circulation, there is no oil mist at high temperature and no water vapor at low temperature, pressure do not rise up when system is running. The system will supply oil automatically at low temperature.
RefrigerantR404A/R23/R14 mixture,optional: R125/R23/R14 mixture
Connection sizeG3/4G3/4G3/4G1G1DN32 PN10DN32 PN10DN40 PN10DN50 PN10DN50 PN10
Water-cooled type W(cooling water@20℃)1100L/H
1.5bar~4bar
1900L/H
1.5bar~4bar
2400L/H
1.5bar~4bar
3200L/H
1.5bar~4bar
4000L/H
1.5bar~4bar
8m³/H
1.5bar~4bar
12m³/H
1.5bar~4bar
20m³/H
1.5bar~4bar
30m³/H
1.5bar~4bar
40m³/H
1.5bar~4bar
Dimension cm55*100*17545*85*13055*100*17555*100*17570*100*175100*150*185205*145*205205*145*205245*145*225300*160*225
Weight kg2602953655706809501400175024003150
Power 380V 50HZ8kW11kW16kW21kW27kW38kW54kW79kW120kW170kW

Working Principle

Ultra high temperature cooling technology can directly cool from a high temperature of 300℃[because only the heat transfer medium in the expansion chamber contacts with oxygen in the air (and the temperature of the expansion tank is between normal temperature and 60℃), which can reduce the risk of heat transfer medium being oxidized and absorbing water in the air. At high temperature, no heat conducting medium evaporates, and continuous temperature control of – 80℃ ~ 190℃, – 70℃ ~ 220℃, – 88℃ ~ 170℃, – 55℃ ~ 250℃ and – 30℃ ~ 300℃ can be realized without pressurization.

Application: Various Reactors (Microchannels, Glass, Jacketed Reactors, etc.), Distillation or Extraction System, Laboratory, University, Research Institute, Aerospace, Automotive Industry, Semiconductor and Electrical Test, Chemical, Pharmaceutical, Petrochemical, Biochemical, Medical, Hospital, R&D Workshop, Aerospace, Biological and Other Industries.

Application: Various Reactors (Microchannels, Glass, Jacketed Reactors, etc.), Distillation or Extraction System, Laboratory, University, Research Institute, Aerospace, Automotive Industry, Semiconductor and Electrical Test, Chemical, Pharmaceutical, Petrochemical, Biochemical, Medical, Hospital, R&D Workshop, Aerospace, Biological and Other Industries.

This model is a water-cooled chiller. Use the mixture of ethylene glycol and water for circulating cooling.

RELATED PRODUCTS

Switch more

loading…

No more to see

Leave a message
Leave a message
1